| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | U-Tube Tank Heater | 150 PSI / 375°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-275-10-024-001 as shown on this page.
Built around a two-pass U-bend bundle, this configuration delivers in-tank heating with boiler water in the tubes for demanding service. The bundle mounts through a collar in the tank wall and heats the surrounding fluid by natural convection. Its envelope centers on a 10-inch diameter shell, 24-inch shell length, and roughly 23-3/8 inches overall in a 2-pass arrangement. That works out to about 27 square feet of heat transfer surface on 3/4-inch O.D. tubes. Material selection covers cast iron bonnets, steel shell, copper tubes, and steel tubesheets. Operating limits are 150 PSI on the shell side, 150 PSI on the tube side, and 375°F maximum temperature. Installations range across hot water storage tanks, hydronic-fed storage systems, and domestic water storage heating. This build is designated 5-275-10-024-001.