DUTY TYPICAL SERIES ADDS CONTROL
Recirculation SU / WU / DSU Continuous small load Turndown matters

Domestic Hot Water Recirculation

The Load That Never Goes Away

A recirculation loop circulates hot water continuously through the distribution system so that any tap delivers hot water quickly. It saves water and improves service, and it changes the heater's duty profile substantially.

It adds a continuous load. The loop loses heat through the pipework all day and all night, and the heater has to make that up. On a building with long runs and modest insulation, that standing load can be a significant fraction of the design duty.

Turndown becomes the design problem. The heater now has to satisfy a large morning peak and a small overnight recirculation load with the same control valve. A valve sized for the peak operates near the bottom of its range for most of the day, which produces hunting and temperature swing.

Legionella control interacts with this. Recirculation systems are usually required to maintain a minimum temperature throughout the loop, and that requirement sets the heater's setpoint and the acceptable temperature drop around the circuit rather than comfort alone.

Scaling accelerates with continuous operation. A heater running continuously at a high wall temperature scales faster than one that cycles. Lowering the medium temperature and adding surface is the usual remedy.

Bell and Gossett heat exchanger serving a domestic hot water recirculation loop

Recirculation Selection

The peak draw and the recirculation load are two different duties the same heater has to serve.

Duty Inputs

  • Peak draw: GPM and duration
  • Recirculation flow: GPM around the loop
  • Loop heat loss: BTU/hr standing
  • Minimum loop temperature: Set by policy or code

Series

  • SU or DSU on steam
  • WU or DWU on a hot water loop
  • Storage with TCS or TCW where peaks are sharp
  • Double-wall where potable
  • Sized for peak and checked at turndown

Design For

  • Wide turndown ratio
  • Continuous overnight load
  • Minimum loop temperature
  • Scaling at continuous operation
  • Control valve range

Related


Bell and Gossett SU Series steam heat exchanger
hot water storage tank heating
potable water heating requirement

Turndown Is the Recirculation Problem

One Valve, Two Very Different Duties

The heater has to deliver the morning peak and then hold a small overnight recirculation load. A control valve sized for the first operates near the bottom of its range for the second, and near the bottom of the range is where valves hunt and outlet temperature swings.

Where the ratio is wide, either a smaller valve in parallel or a storage vessel that lets the heater cycle rather than modulate is worth designing in. On steam, wide turndown also brings the risk of stall.

Continuous Operation Accelerates Scaling

A heater serving a recirculation loop never fully stops, so the tube wall is hot all the time. On hard water that scales faster than a heater that cycles and cools between draws.

Lowering the medium temperature and adding surface reduces the wall temperature and slows the scaling. It is more effective than treating the symptom with more frequent descaling.

Common FAQs

It adds a continuous small load on top of a large intermittent one, which widens the turndown ratio the control valve has to cover. A valve sized only for the peak behaves badly at the recirculation load.

Yes, through standing heat loss from the loop, which the heater makes up continuously. Good pipework insulation and a sensible loop temperature limit how much.

Requirements to maintain a minimum temperature throughout the loop set the heater setpoint and the acceptable temperature drop around the circuit, rather than comfort alone. That constrains both the heater and the loop design.

Because it runs continuously, so the tube wall is always hot, and scale forms preferentially on hot surfaces. Reducing the medium temperature and adding surface slows it more effectively than descaling more often.