| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | N/A / N/A | Six Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n SU203-6 as shown on this page.
A removable U-tube bundle gives this configuration the thermal and mechanical margin expected of SU/WU equipment in steam-to-liquid heating. Steam condenses in the single-pass shell while the heated fluid travels the tubes. Dimensionally it is a 20-inch shell unit, 36-inch shell length, and roughly 49-3/4 inches overall in a 6-pass arrangement. That works out to about 182 square feet of heat transfer surface on 3/4-inch O.D. tubes. As furnished, materials include cast iron or brass bonnets, steel shell, copper tubes, and steel tubesheets. Operating limits are N/A on the shell side, N/A on the tube side, and N/A maximum temperature. This build is designated SU203-6. Typical duty includes instantaneous domestic water heating, radiant panel and snow-melt converters, and building comfort heating.