| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 375°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-260-18-048-001 as shown on this page.
The SU/WU platform pairs a removable U-tube bundle with proven shell-side baffling, and this configuration applies that design to steam-to-liquid heating. Steam condenses in the single-pass shell while the heated fluid travels the tubes. Dimensionally it is a 18-inch shell unit, 48-inch shell length, and roughly 60-1/2 inches overall in a 2-pass arrangement. That works out to about 195 square feet of heat transfer surface on 3/4-inch O.D. tubes. Standard construction uses cast iron bonnets, steel shell, copper tubes, and steel tubesheets. Design ratings run to 150 PSI on the shell side, 150 PSI on the tube side, and 375°F maximum temperature. Typical duty includes swimming pool heating, instantaneous domestic water heating, and radiant panel and snow-melt converters. This build is designated 5-260-18-048-001.