| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 375°F | Six Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-268-10-096-003 as shown on this page.
Configured for high-temperature water heating, 5-268-10-096-003 carries the removable U-tube bundle construction that defines the HTWU range. High-temperature water flows through the tube side, so the heads rather than the shell set the pressure limit. Dimensionally it is a 10-inch shell unit, 96-inch shell length, and roughly 101-3/8 inches overall in a 6-pass arrangement. That works out to about 92 square feet of heat transfer surface on 3/4-inch O.D. tubes. Standard construction uses cast iron bonnets, steel shell, copper tubes, and steel tubesheets. Operating limits are 150 PSI on the shell side, 400 PSI on the tube side, and 375°F maximum temperature. Installations range across campus and district energy systems, high-temperature hot water distribution, and industrial process heating.