A removable U-tube bundle gives 5-268-04-084-001 the thermal and mechanical margin expected of HTWU equipment in high-temperature water heating. High-temperature water flows through the tube side, so the heads rather than the shell set the pressure limit. Physically, the unit runs a 4-inch shell, 84-inch shell length, and roughly 88-5/8 inches overall in a 2-pass arrangement. That works out to about 16.3 square feet of heat transfer surface on 3/4-inch O.D. tubes. Material selection covers cast iron bonnets, steel shell, copper tubes, and steel tubesheets. On the ratings side, expect 150 PSI on the shell side, 400 PSI on the tube side, and 375°F maximum temperature. The series sees regular use in industrial process heating, high-temperature hot water distribution, and converter duty on HTHW loops.