| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 375°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-268-04-072-001 as shown on this page.
Configured for high-temperature water heating, this configuration carries the removable U-tube bundle construction that defines the HTWU range. High-temperature water flows through the tube side, so the heads rather than the shell set the pressure limit. Physically, the unit runs a 4-inch shell, 72-inch shell length, and roughly 76-5/8 inches overall in a 2-pass arrangement. That works out to about 13.9 square feet of heat transfer surface on 3/4-inch O.D. tubes. Material selection covers cast iron bonnets, steel shell, copper tubes, and steel tubesheets. Operating limits are 150 PSI on the shell side, 400 PSI on the tube side, and 375°F maximum temperature. This build is designated 5-268-04-072-001.