| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 375°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-268-04-060-001 as shown on this page.
The HTWU platform pairs a removable U-tube bundle with proven shell-side baffling, and 5-268-04-060-001 applies that design to high-temperature water heating. High-temperature water flows through the tube side, so the heads rather than the shell set the pressure limit. Physically, the unit runs a 4-inch shell, 60-inch shell length, and roughly 64-5/8 inches overall in a 2-pass arrangement. That works out to about 11.5 square feet of heat transfer surface on 3/4-inch O.D. tubes. Material selection covers cast iron bonnets, steel shell, copper tubes, and steel tubesheets. The unit is rated for 150 PSI on the shell side, 400 PSI on the tube side, and 375°F maximum temperature. Installations range across industrial process heating, converter duty on HTHW loops, and campus and district energy systems.