| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 375°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-268-04-036-001 as shown on this page.
5-268-04-036-001 is a HTWU unit built on a removable U-tube bundle for high-temperature water heating. High-temperature water flows through the tube side, so the heads rather than the shell set the pressure limit. The configuration measures 4 inches across the shell, 36-inch shell length, and roughly 40-5/8 inches overall in a 2-pass arrangement. That works out to about 6.8 square feet of heat transfer surface on 3/4-inch O.D. tubes. The build specifies cast iron bonnets, steel shell, copper tubes, and steel tubesheets. The unit is rated for 150 PSI on the shell side, 400 PSI on the tube side, and 375°F maximum temperature. Installations range across high-temperature hot water distribution, campus and district energy systems, and industrial process heating.