| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 300°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n WU165-210 as shown on this page.
For liquid-to-liquid heating and cooling, the SU/WU line offers a removable U-tube bundle design; this configuration sits within that range. Pumped boiler water circulates through the baffled shell against the tube-side fluid. Dimensionally it is a 16-inch shell unit, 60-inch shell length, and roughly 69-3/4 inches overall in a 2-pass arrangement. That works out to about 188 square feet of heat transfer surface on 3/4-inch O.D. tubes. Standard construction uses cast iron or brass bonnets, steel shell, copper tubes, and steel or brass tubesheets. The unit is rated for 150 PSI on the shell side, 125 PSI on the tube side, and 300°F maximum temperature. The series sees regular use in condensate cooling, oil cooling and snow melting, and pool and storage-tower heating. This build is designated WU165-210.