| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 300°F | Four Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-265-12-096-002 as shown on this page.
The SU/WU platform pairs a removable U-tube bundle with proven shell-side baffling, and this configuration applies that design to liquid-to-liquid heating and cooling. Pumped boiler water circulates through the baffled shell against the tube-side fluid. The configuration measures 12 inches across the shell, 96-inch shell length, and roughly 104-1/2 inches overall in a 4-pass arrangement. That works out to about 160 square feet of heat transfer surface on 3/4-inch O.D. tubes. That combination is cataloged as 5-265-12-096-002. Material selection covers cast iron bonnets, steel shell, copper tubes, and steel tubesheets. Design ratings run to 150 PSI on the shell side, 125 PSI on the tube side, and 300°F maximum temperature. Common applications are hydronic HVAC converters, pool and storage-tower heating, and oil cooling and snow melting.