| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 300°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-265-12-072-001 as shown on this page.
A removable U-tube bundle gives this configuration the thermal and mechanical margin expected of SU/WU equipment in liquid-to-liquid heating and cooling. Pumped boiler water circulates through the baffled shell against the tube-side fluid. Physically, the unit runs a 12-inch shell, 72-inch shell length, and roughly 80-1/2 inches overall in a 2-pass arrangement. That works out to about 126 square feet of heat transfer surface on 3/4-inch O.D. tubes. Material selection covers cast iron bonnets, steel shell, copper tubes, and steel tubesheets. Design ratings run to 150 PSI on the shell side, 125 PSI on the tube side, and 300°F maximum temperature. This build is designated 5-265-12-072-001. Common applications are hydronic HVAC converters, condensate cooling, and pool and storage-tower heating.