| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 375°F | Four Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-267-10-048-002 as shown on this page.
This configuration is a Diamondback DSU/DWU unit built on a double-wall U-tube bundle for liquid-to-liquid transfer with cross-contamination protection. Each tube is vented to atmosphere through a diamond-pattern air gap, so a failure in either wall reports itself outside the unit. Its envelope centers on a 10-inch diameter shell, 48-inch shell length in a 4-pass arrangement. It carries 3/4-inch O.D. tubes. Standard construction uses cast iron bonnets, steel shell, copper (double wall) tubes, and naval brass tubesheets. Design ratings run to 150 PSI on the shell side, 125 PSI on the tube side, and 375°F maximum temperature. This build is designated 5-267-10-048-002. Installations range across process cooling where mixing cannot be tolerated, potable water heating and cooling, and glycol-to-potable loops.