| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n CHXS884-2L as shown on this page.
A fixed-tubesheet bundle gives this configuration the thermal and mechanical margin expected of CHXS compact equipment in compact liquid cooling in corrosive service. It shares the compact CHX envelope while targeting service that would attack a standard cooler. The configuration measures 8 inches across the shell, 84-inch shell length in a 2-pass arrangement. It carries 3/4-inch O.D. tubes. As furnished, materials include cast iron bonnets, steel shell, copper tubes, and brass tubesheets. The unit is rated for 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. Installations range across hydraulic and lube oil cooling, mechanical seal cooling, and deionized and treated water cooling. This build is designated CHXS884-2L.