| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | One Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-160-08-036-002 as shown on this page.
The CHXS compact platform pairs a fixed-tubesheet bundle with proven shell-side baffling, and this configuration applies that design to compact liquid cooling in corrosive service. It shares the compact CHX envelope while targeting service that would attack a standard cooler. The configuration measures 8 inches across the shell, 36-inch shell length, and roughly 43 inches overall in a 1-pass arrangement. That works out to about 62 square feet of heat transfer surface on 3/4-inch O.D. tubes. Material selection covers cast iron bonnets, steel shell, copper tubes, and brass tubesheets. Design ratings run to 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. This build is designated 5-160-08-036-002.