| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-160-06-024-004 as shown on this page.
For compact liquid cooling in corrosive service, the CHXS compact line offers a fixed-tubesheet bundle design; 5-160-06-024-004 sits within that range. It shares the compact CHX envelope while targeting service that would attack a standard cooler. Physically, the unit runs a 6-inch shell, 24-inch shell length, and roughly 29-3/4 inches overall in a 2-pass arrangement. That works out to about 23 square feet of heat transfer surface on 3/4-inch O.D. tubes. Material selection covers cast iron bonnets, steel shell, copper tubes, and brass tubesheets. Operating limits are 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. The series sees regular use in chemical and food process cooling, deionized and treated water cooling, and hydraulic and lube oil cooling.