| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | One Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-030-06-036-002 as shown on this page.
A fixed-tubesheet bundle gives this configuration the thermal and mechanical margin expected of CHX compact equipment in compact liquid cooling. Small-diameter tubes pack maximum surface into a short shell, keeping the mounting footprint tight. The configuration measures 6 inches across the shell, 36-inch shell length, and roughly 41 inches overall in a 1-pass arrangement. That works out to about 34 square feet of heat transfer surface on 3/4-inch O.D. tubes. Standard construction uses cast iron bonnets, brass shell, copper tubes, and brass tubesheets. The unit is rated for 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. Typical duty includes mechanical seal cooling, hydraulic and lube oil cooling, and engine jacket water cooling. This build is designated 5-030-06-036-002.