| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | One Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-030-06-036-001 as shown on this page.
For compact liquid cooling, the CHX compact line offers a fixed-tubesheet bundle design; this configuration sits within that range. Small-diameter tubes pack maximum surface into a short shell, keeping the mounting footprint tight. Its envelope centers on a 6-inch diameter shell, 36-inch shell length, and roughly 41 inches overall in a 1-pass arrangement. That works out to about 34 square feet of heat transfer surface on 3/4-inch O.D. tubes. Standard construction uses cast iron bonnets, brass shell, copper tubes, and brass tubesheets. Operating limits are 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. This build is designated 5-030-06-036-001. Typical duty includes mechanical seal cooling, injection molding machine cooling, and engine jacket water cooling.