| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-030-05-014-003 as shown on this page.
The CHX compact platform pairs a fixed-tubesheet bundle with proven shell-side baffling, and 5-030-05-014-003 applies that design to compact liquid cooling. Small-diameter tubes pack maximum surface into a short shell, keeping the mounting footprint tight. The configuration measures 5 inches across the shell, 14-inch shell length, and roughly 18-5/16 inches overall in a 2-pass arrangement. That works out to about 9.1 square feet of heat transfer surface on 3/4-inch O.D. tubes. As furnished, materials include cast iron bonnets, brass shell, copper tubes, and brass tubesheets. Operating limits are 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. Common applications are hydraulic and lube oil cooling, injection molding machine cooling, and engine jacket water cooling.