TCW-836

Bell & Gossett
Product Style Ratings Configuration
Heat Exchanger U-Tube Tank Heater 150 PSI / 375°F Two Pass
TCW-836 -Download Datasheet

Note: Unit pictured is representative of standard unit and may not exactly depict p/n TCW-836 as shown on this page.

TCW-836

Description

this configuration is a TCS/TCW tank heater unit built on a two-pass U-bend bundle for in-tank heating with boiler water in the tubes. The bundle mounts through a collar in the tank wall and heats the surrounding fluid by natural convection. Physically, the unit runs a 8-inch shell, 36-inch shell length, and roughly 34-1/4 inches overall in a 2-pass arrangement. That works out to about 23 square feet of heat transfer surface on 3/4-inch O.D. tubes. That combination is cataloged as TCW-836. As furnished, materials include cast iron or brass bonnets, steel shell, copper tubes, and steel or brass tubesheets. Design ratings run to 150 PSI on the shell side, 150 PSI on the tube side, and 375°F maximum temperature.

Product Overview

Part Number:
TCW-836
Series:
TCW
Brand:
Bell & Gossett

Configuration & Size

Shell Diameter:
8"
Shell Length:
36"
Cooling Tube Diameter:
3/4" O.D.
Overall Length:
34-1/4"
Tube Side Connections:
3.0" NPT
Tubeside Passes:
2-Pass

Materials of Construction

  • Bonnets: Cast Iron or Brass
  • Shell: Steel
  • Tubes: Copper
  • Tubesheet: Steel or Brass

Rating

  • Max Shell Pressure: 150 PSI
  • Max Temperature: 375°F
  • Max Tube Pressure: 150 PSI