| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 375°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-275-14-066-001 as shown on this page.
For in-tank heating with boiler water in the tubes, the TCS/TCW tank heater line offers a two-pass U-bend bundle design; 5-275-14-066-001 sits within that range. The bundle mounts through a collar in the tank wall and heats the surrounding fluid by natural convection. Its envelope centers on a 14-inch diameter shell, 66-inch shell length, and roughly 67-1/2 inches overall in a 2-pass arrangement. That works out to about 161 square feet of heat transfer surface on 3/4-inch O.D. tubes. The build specifies cast iron bonnets, steel shell, copper tubes, and steel tubesheets. Design ratings run to 150 PSI on the shell side, 150 PSI on the tube side, and 375°F maximum temperature. Installations range across hydronic-fed storage systems, process tank heating, and domestic water storage heating.