| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 375°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-277-08-096-001 as shown on this page.
5-277-08-096-001 is a Diamondback tank heater unit built on a double-wall two-pass U-bend bundle for in-tank heating with boiler water in the tubes and cross-contamination protection. The vented air gap between tube walls gives a visible telltale leak rather than allowing boiler water and tank contents to mix. Its envelope centers on a 8-inch diameter shell in a 2-pass arrangement. It carries 3/4-inch O.D. tubes. The build specifies cast iron bonnets, steel shell, and copper (double wall) tubes. Design ratings run to 150 PSI on the shell side, 150 PSI on the tube side, and 375°F maximum temperature. Common applications are domestic water storage under double-wall codes, institutional and health care water storage, and glycol-fed storage heating.