| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 375°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-277-04-096-001 as shown on this page.
The Diamondback tank heater platform pairs a double-wall two-pass U-bend bundle with proven shell-side baffling, and this configuration applies that design to in-tank heating with boiler water in the tubes and cross-contamination protection. The vented air gap between tube walls gives a visible telltale leak rather than allowing boiler water and tank contents to mix. The configuration measures 4 inches across the shell in a 2-pass arrangement. It carries 3/4-inch O.D. tubes. Material selection covers cast iron bonnets, steel shell, and copper (double wall) tubes. Operating limits are 150 PSI on the shell side, 150 PSI on the tube side, and 375°F maximum temperature. Common applications are glycol-fed storage heating, institutional and health care water storage, and domestic water storage under double-wall codes. This build is designated 5-277-04-096-001.