| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 375°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n SU209-2 as shown on this page.
The SU/WU platform pairs a removable U-tube bundle with proven shell-side baffling, and this configuration applies that design to steam-to-liquid heating. Steam condenses in the single-pass shell while the heated fluid travels the tubes. Its envelope centers on a 20-inch diameter shell, 108-inch shell length, and roughly 121-3/4 inches overall in a 2-pass arrangement. That works out to about 582 square feet of heat transfer surface on 3/4-inch O.D. tubes. The build specifies cast iron or brass bonnets, steel shell, copper tubes, and brass tubesheets. Operating limits are 150 PSI on the shell side, 150 PSI on the tube side, and 375°F maximum temperature. This build is designated SU209-2.