| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 375°F | Four Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-261-20-108-002 as shown on this page.
Configured for steam-to-liquid heating, this configuration carries the removable U-tube bundle construction that defines the SU/WU range. Steam condenses in the single-pass shell while the heated fluid travels the tubes. Dimensionally it is a 20-inch shell unit, 108-inch shell length, and roughly 121-3/4 inches overall in a 4-pass arrangement. That works out to about 565 square feet of heat transfer surface on 3/4-inch O.D. tubes. Material selection covers cast iron bonnets, steel shell, copper tubes, and brass tubesheets. On the ratings side, expect 150 PSI on the shell side, 150 PSI on the tube side, and 375°F maximum temperature. This build is designated 5-261-20-108-002. Installations range across swimming pool heating, instantaneous domestic water heating, and radiant panel and snow-melt converters.