| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 375°F | Six Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-261-10-096-003 as shown on this page.
Built around a removable U-tube bundle, 5-261-10-096-003 delivers steam-to-liquid heating for demanding service. Steam condenses in the single-pass shell while the heated fluid travels the tubes. Dimensionally it is a 10-inch shell unit, 96-inch shell length, and roughly 101 inches overall in a 6-pass arrangement. That works out to about 92 square feet of heat transfer surface on 3/4-inch O.D. tubes. As furnished, materials include cast iron bonnets, steel shell, copper tubes, and brass tubesheets. Design ratings run to 150 PSI on the shell side, 150 PSI on the tube side, and 375°F maximum temperature. Common applications are swimming pool heating, building comfort heating, and instantaneous domestic water heating.