| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 375°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-260-10-024-001 as shown on this page.
Built around a removable U-tube bundle, this configuration delivers steam-to-liquid heating for demanding service. Steam condenses in the single-pass shell while the heated fluid travels the tubes. The configuration measures 10 inches across the shell, 24-inch shell length, and roughly 29 inches overall in a 2-pass arrangement. That works out to about 27 square feet of heat transfer surface on 3/4-inch O.D. tubes. The build specifies cast iron bonnets, steel shell, copper tubes, and steel tubesheets. Design ratings run to 150 PSI on the shell side, 125 PSI on the tube side, and 375°F maximum temperature. This build is designated 5-260-10-024-001. Typical duty includes instantaneous domestic water heating, radiant panel and snow-melt converters, and building comfort heating.