| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 375°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-260-04-060-011 as shown on this page.
Built around a removable U-tube bundle, this configuration delivers steam-to-liquid heating for demanding service. Steam condenses in the single-pass shell while the heated fluid travels the tubes. The configuration measures 4 inches across the shell, 60-inch shell length, and roughly 65 inches overall in a 2-pass arrangement. That works out to about 11.5 square feet of heat transfer surface on 3/4-inch O.D. tubes. The build specifies cast iron bonnets, steel shell, copper tubes, and steel tubesheets. The unit is rated for 150 PSI on the shell side, 150 PSI on the tube side, and 375°F maximum temperature. Typical duty includes instantaneous domestic water heating, radiant panel and snow-melt converters, and building comfort heating. This build is designated 5-260-04-060-011.