| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 375°F | Six Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-262-06-048-003 as shown on this page.
A double-wall U-tube bundle gives this configuration the thermal and mechanical margin expected of Diamondback DSU/DWU equipment in steam-to-liquid heating with cross-contamination protection. An atmospheric air gap between the inner and outer tube vents any breach to the outside, giving a visible telltale leak instead of silent mixing. Dimensionally it is a 6-inch shell unit, 48-inch shell length in a 6-pass arrangement. It carries 3/4-inch O.D. tubes. That combination is cataloged as 5-262-06-048-003. Material selection covers cast iron bonnets, steel shell, copper (double wall) tubes, and naval brass tubesheets. Operating limits are 150 PSI on the shell side, 150 PSI on the tube side, and 375°F maximum temperature. Common applications are food and beverage process heating, potable water heating, and health care and institutional plumbing.