| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 300°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n WU149-28 as shown on this page.
WU149-28 is a SU/WU unit built on a removable U-tube bundle for liquid-to-liquid heating and cooling. Pumped boiler water circulates through the baffled shell against the tube-side fluid. Physically, the unit runs a 14-inch shell, 108-inch shell length, and roughly 117-1/8 inches overall in a 2-pass arrangement. That works out to about 263 square feet of heat transfer surface on 3/4-inch O.D. tubes. As furnished, materials include cast iron or brass bonnets, steel shell, copper tubes, and steel or brass tubesheets. Design ratings run to 150 PSI on the shell side, 125 PSI on the tube side, and 300°F maximum temperature. Typical duty includes hydronic HVAC converters, pool and storage-tower heating, and oil cooling and snow melting.