| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 300°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-266-12-108-001 as shown on this page.
The SU/WU platform pairs a removable U-tube bundle with proven shell-side baffling, and this configuration applies that design to liquid-to-liquid heating and cooling. Pumped boiler water circulates through the baffled shell against the tube-side fluid. Its envelope centers on a 12-inch diameter shell, 108-inch shell length, and roughly 116-1/2 inches overall in a 2-pass arrangement. That works out to about 191 square feet of heat transfer surface on 3/4-inch O.D. tubes. Material selection covers cast iron bonnets, steel shell, copper tubes, and brass tubesheets. The unit is rated for 150 PSI on the shell side, 125 PSI on the tube side, and 300°F maximum temperature. This build is designated 5-266-12-108-001. The series sees regular use in pool and storage-tower heating, condensate cooling, and hydronic HVAC converters.