| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 300°F | Four Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-266-06-060-002 as shown on this page.
A removable U-tube bundle gives this configuration the thermal and mechanical margin expected of SU/WU equipment in liquid-to-liquid heating and cooling. Pumped boiler water circulates through the baffled shell against the tube-side fluid. Its envelope centers on a 6-inch diameter shell, 60-inch shell length, and roughly 64-1/8 inches overall in a 4-pass arrangement. That works out to about 22.1 square feet of heat transfer surface on 3/4-inch O.D. tubes. That combination is cataloged as 5-266-06-060-002. Material selection covers cast iron bonnets, steel shell, copper tubes, and brass tubesheets. The unit is rated for 150 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. Installations range across oil cooling and snow melting, pool and storage-tower heating, and condensate cooling.