| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 300°F | Four Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-265-12-060-002 as shown on this page.
Configured for liquid-to-liquid heating and cooling, 5-265-12-060-002 carries the removable U-tube bundle construction that defines the SU/WU range. Pumped boiler water circulates through the baffled shell against the tube-side fluid. The configuration measures 12 inches across the shell, 60-inch shell length, and roughly 68-1/2 inches overall in a 4-pass arrangement. That works out to about 98 square feet of heat transfer surface on 3/4-inch O.D. tubes. As furnished, materials include cast iron bonnets, steel shell, copper tubes, and steel tubesheets. On the ratings side, expect 150 PSI on the shell side, 125 PSI on the tube side, and 300°F maximum temperature. Installations range across oil cooling and snow melting, condensate cooling, and hydronic HVAC converters.