| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 300°F | Four Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-265-08-096-002 as shown on this page.
Configured for liquid-to-liquid heating and cooling, this configuration carries the removable U-tube bundle construction that defines the SU/WU range. Pumped boiler water circulates through the baffled shell against the tube-side fluid. Dimensionally it is a 8-inch shell unit, 96-inch shell length, and roughly 101 inches overall in a 4-pass arrangement. That works out to about 67 square feet of heat transfer surface on 3/4-inch O.D. tubes. Material selection covers cast iron bonnets, steel shell, copper tubes, and steel tubesheets. Operating limits are 150 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. This build is designated 5-265-08-096-002. Common applications are pool and storage-tower heating, condensate cooling, and hydronic HVAC converters.