| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 300°F | Four Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-265-06-096-002 as shown on this page.
For liquid-to-liquid heating and cooling, the SU/WU line offers a removable U-tube bundle design; this configuration sits within that range. Pumped boiler water circulates through the baffled shell against the tube-side fluid. Dimensionally it is a 6-inch shell unit, 96-inch shell length, and roughly 100-1/8 inches overall in a 4-pass arrangement. That works out to about 36.2 square feet of heat transfer surface on 3/4-inch O.D. tubes. As furnished, materials include cast iron bonnets, steel shell, copper tubes, and steel tubesheets. Design ratings run to 150 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. Common applications are pool and storage-tower heating, oil cooling and snow melting, and hydronic HVAC converters. This build is designated 5-265-06-096-002.