| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 150 PSI / 375°F | One Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-151-14-120-001 as shown on this page.
This configuration is a OC straight tube unit built on a removable straight-tube bundle for general industrial liquid-to-liquid heat transfer. An internally packed floating rear tubesheet absorbs differential expansion, and the bundle pulls for straight-through mechanical tube cleaning. The configuration measures 14 inches across the shell, 120-inch shell length, and roughly 137 inches overall in a 1-pass arrangement. That works out to about 379 square feet of heat transfer surface on 5/8-inch O.D. tubes. Material selection covers cast iron bonnets, steel shell, copper tubes, and steel tubesheets. Operating limits are 150 PSI on the shell side, 150 PSI on the tube side, and 375°F maximum temperature. This build is designated 5-151-14-120-001.