| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-160-08-072-003 as shown on this page.
The CHXS compact platform pairs a fixed-tubesheet bundle with proven shell-side baffling, and this configuration applies that design to compact liquid cooling in corrosive service. It shares the compact CHX envelope while targeting service that would attack a standard cooler. The configuration measures 8 inches across the shell, 72-inch shell length, and roughly 78-1/2 inches overall in a 2-pass arrangement. That works out to about 124 square feet of heat transfer surface on 3/4-inch O.D. tubes. That combination is cataloged as 5-160-08-072-003. Standard construction uses cast iron bonnets, steel shell, copper tubes, and brass tubesheets. Operating limits are 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature.