| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | Four Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-160-08-060-006 as shown on this page.
This configuration is a CHXS compact unit built on a fixed-tubesheet bundle for compact liquid cooling in corrosive service. It shares the compact CHX envelope while targeting service that would attack a standard cooler. The configuration measures 8 inches across the shell, 60-inch shell length, and roughly 66-3/4 inches overall in a 4-pass arrangement. That works out to about 103 square feet of heat transfer surface on 3/4-inch O.D. tubes. Standard construction uses cast iron bonnets, steel shell, copper tubes, and brass tubesheets. On the ratings side, expect 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. This build is designated 5-160-08-060-006. Typical duty includes hydraulic and lube oil cooling, mechanical seal cooling, and chemical and food process cooling.