| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | One Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-160-08-048-002 as shown on this page.
For compact liquid cooling in corrosive service, the CHXS compact line offers a fixed-tubesheet bundle design; 5-160-08-048-002 sits within that range. It shares the compact CHX envelope while targeting service that would attack a standard cooler. Dimensionally it is a 8-inch shell unit, 48-inch shell length, and roughly 55 inches overall in a 1-pass arrangement. That works out to about 82 square feet of heat transfer surface on 3/4-inch O.D. tubes. The build specifies cast iron bonnets, steel shell, copper tubes, and brass tubesheets. On the ratings side, expect 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. Installations range across deionized and treated water cooling, chemical and food process cooling, and mechanical seal cooling.