| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | One Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-160-06-024-001 as shown on this page.
Built around a fixed-tubesheet bundle, this configuration delivers compact liquid cooling in corrosive service for demanding service. It shares the compact CHX envelope while targeting service that would attack a standard cooler. Physically, the unit runs a 6-inch shell, 24-inch shell length, and roughly 29 inches overall in a 1-pass arrangement. That works out to about 23 square feet of heat transfer surface on 3/4-inch O.D. tubes. That combination is cataloged as 5-160-06-024-001. Material selection covers cast iron bonnets, steel shell, copper tubes, and brass tubesheets. Design ratings run to 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. Common applications are chemical and food process cooling, deionized and treated water cooling, and mechanical seal cooling.