| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-160-05-024-004 as shown on this page.
Configured for compact liquid cooling in corrosive service, 5-160-05-024-004 carries the fixed-tubesheet bundle construction that defines the CHXS compact range. It shares the compact CHX envelope while targeting service that would attack a standard cooler. The configuration measures 5 inches across the shell, 24-inch shell length, and roughly 28-5/16 inches overall in a 2-pass arrangement. That works out to about 16 square feet of heat transfer surface on 3/4-inch O.D. tubes. As furnished, materials include cast iron bonnets, steel shell, copper tubes, and brass tubesheets. Design ratings run to 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. The series sees regular use in chemical and food process cooling, deionized and treated water cooling, and mechanical seal cooling.