| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-160-04-024-003 as shown on this page.
Configured for compact liquid cooling in corrosive service, this configuration carries the fixed-tubesheet bundle construction that defines the CHXS compact range. It shares the compact CHX envelope while targeting service that would attack a standard cooler. Dimensionally it is a 4-inch shell unit, 24-inch shell length, and roughly 27-5/8 inches overall in a 2-pass arrangement. That works out to about 14.1 square feet of heat transfer surface on 5/8-inch O.D. tubes. That combination is cataloged as 5-160-04-024-003. The build specifies cast iron bonnets, steel shell, copper tubes, and brass tubesheets. Operating limits are 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. Common applications are mechanical seal cooling, deionized and treated water cooling, and chemical and food process cooling.