| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-160-03-014-004 as shown on this page.
Built around a fixed-tubesheet bundle, this configuration delivers compact liquid cooling in corrosive service for demanding service. It shares the compact CHX envelope while targeting service that would attack a standard cooler. The configuration measures 3 inches across the shell, 14-inch shell length, and roughly 17-1/4 inches overall in a 2-pass arrangement. That works out to about 4.3 square feet of heat transfer surface on 5/8-inch O.D. tubes. As furnished, materials include cast iron bonnets, steel shell, copper tubes, and brass tubesheets. Operating limits are 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. This build is designated 5-160-03-014-004. The series sees regular use in hydraulic and lube oil cooling, mechanical seal cooling, and chemical and food process cooling.