| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | Four Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n CHX660-4S as shown on this page.
A fixed-tubesheet bundle gives this configuration the thermal and mechanical margin expected of CHX compact equipment in compact liquid cooling. Small-diameter tubes pack maximum surface into a short shell, keeping the mounting footprint tight. The configuration measures 6 inches across the shell, 60-inch shell length, and roughly 65 inches overall in a 4-pass arrangement. That works out to about 56 square feet of heat transfer surface on 3/4-inch O.D. tubes. As furnished, materials include cast iron bonnets, brass shell, copper tubes, and brass tubesheets. Design ratings run to 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. This build is designated CHX660-4S. Typical duty includes mechanical seal cooling, hydraulic and lube oil cooling, and injection molding machine cooling.