| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | One Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n CHX436-1L as shown on this page.
A fixed-tubesheet bundle gives this configuration the thermal and mechanical margin expected of CHX compact equipment in compact liquid cooling. Small-diameter tubes pack maximum surface into a short shell, keeping the mounting footprint tight. Physically, the unit runs a 4-inch shell, 36-inch shell length, and roughly 40 inches overall in a 1-pass arrangement. That works out to about 21.2 square feet of heat transfer surface on 5/8-inch O.D. tubes. Material selection covers cast iron bonnets, brass shell, copper tubes, and brass tubesheets. Design ratings run to 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. Installations range across engine jacket water cooling, injection molding machine cooling, and mechanical seal cooling. This build is designated CHX436-1L.