| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | One Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n CHX424-1L as shown on this page.
Configured for compact liquid cooling, this configuration carries the fixed-tubesheet bundle construction that defines the CHX compact range. Small-diameter tubes pack maximum surface into a short shell, keeping the mounting footprint tight. Physically, the unit runs a 4-inch shell, 24-inch shell length, and roughly 28 inches overall in a 1-pass arrangement. That works out to about 14.1 square feet of heat transfer surface on 5/8-inch O.D. tubes. That combination is cataloged as CHX424-1L. Material selection covers cast iron bonnets, brass shell, copper tubes, and brass tubesheets. Design ratings run to 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. Typical duty includes hydraulic and lube oil cooling, engine jacket water cooling, and injection molding machine cooling.