| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | One Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-030-05-036-001 as shown on this page.
This configuration is a CHX compact unit built on a fixed-tubesheet bundle for compact liquid cooling. Small-diameter tubes pack maximum surface into a short shell, keeping the mounting footprint tight. Physically, the unit runs a 5-inch shell, 36-inch shell length, and roughly 40-1/2 inches overall in a 1-pass arrangement. That works out to about 24 square feet of heat transfer surface on 3/4-inch O.D. tubes. Standard construction uses cast iron bonnets, brass shell, copper tubes, and brass tubesheets. The unit is rated for 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. This build is designated 5-030-05-036-001. Typical duty includes mechanical seal cooling, engine jacket water cooling, and hydraulic and lube oil cooling.