| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | Four Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-030-05-014-006 as shown on this page.
Configured for compact liquid cooling, this configuration carries the fixed-tubesheet bundle construction that defines the CHX compact range. Small-diameter tubes pack maximum surface into a short shell, keeping the mounting footprint tight. Physically, the unit runs a 5-inch shell, 14-inch shell length, and roughly 18-3/8 inches overall in a 4-pass arrangement. That works out to about 9.1 square feet of heat transfer surface on 3/4-inch O.D. tubes. Standard construction uses cast iron bonnets, brass shell, copper tubes, and brass tubesheets. Operating limits are 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. Common applications are hydraulic and lube oil cooling, engine jacket water cooling, and mechanical seal cooling. This build is designated 5-030-05-014-006.