| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | Two Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-030-04-024-004 as shown on this page.
For compact liquid cooling, the CHX compact line offers a fixed-tubesheet bundle design; this configuration sits within that range. Small-diameter tubes pack maximum surface into a short shell, keeping the mounting footprint tight. Its envelope centers on a 4-inch diameter shell, 24-inch shell length, and roughly 27-5/8 inches overall in a 2-pass arrangement. That works out to about 14.1 square feet of heat transfer surface on 5/8-inch O.D. tubes. That combination is cataloged as 5-030-04-024-004. The build specifies cast iron bonnets, brass shell, copper tubes, and brass tubesheets. On the ratings side, expect 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. Installations range across injection molding machine cooling, engine jacket water cooling, and hydraulic and lube oil cooling.