| Product | Style | Ratings | Configuration |
|---|---|---|---|
| Heat Exchanger | Shell & Tube | 300 PSI / 300°F | Four Pass |
-Download Datasheet
Note: Unit pictured is representative of standard unit and may not exactly depict p/n 5-030-04-014-005 as shown on this page.
For compact liquid cooling, the CHX compact line offers a fixed-tubesheet bundle design; 5-030-04-014-005 sits within that range. Small-diameter tubes pack maximum surface into a short shell, keeping the mounting footprint tight. Physically, the unit runs a 4-inch shell, 14-inch shell length, and roughly 17-5/8 inches overall in a 4-pass arrangement. That works out to about 8.3 square feet of heat transfer surface on 5/8-inch O.D. tubes. Standard construction uses cast iron bonnets, brass shell, copper tubes, and brass tubesheets. On the ratings side, expect 300 PSI on the shell side, 150 PSI on the tube side, and 300°F maximum temperature. Typical duty includes injection molding machine cooling, hydraulic and lube oil cooling, and engine jacket water cooling.